Compressed Air System Calculator

Static · formula-only · worked example computed when this page was built · no live data

The Compressed Air System Calculator sizes the compressor (kW/HP) and air receiver for a plant's demand, pressure, and duty cycle. Example: for a 10 m³/min plant demand at 7 barg and 60% duty, with a 1.25 design safety factor, at 88% compressor efficiency, Recommended compressor = 132 kW, Recommended compressor (HP) = 177 HP, Air receiver = 20.27 m³ (per ISO 1217 | ISO 8573-1 | ASME B31.3 | CAGI).

How it works

Computed from your inputs per ISO 1217 | ISO 8573-1 | ASME B31.3 | CAGI. Anything the worked example does not state uses this calculator's standard default; the interactive version shows every input and lets you change it.

Worked example (HVAC & Cooling)

Inputs: a 10 m³/min plant demand at 7 barg and 60% duty, with a 1.25 design safety factor, at 88% compressor efficiency.

ResultValue
Recommended compressor132 kW
Recommended compressor (HP)177 HP
Air receiver20.27 m³

Computed by WorkHive's calculation engine when this page was built; standard: ISO 1217 | ISO 8573-1 | ASME B31.3 | CAGI.

How to use this calculator

  1. Read the worked example. It uses a 10 m³/min plant demand at 7 barg and 60% duty, with a 1.25 design safety factor, at 88% compressor efficiency and shows every number in the method.
  2. Follow the formula with your own figures: it returns Recommended compressor, Recommended, Air receiver, computed per ISO 1217 | PSME Code | ASME B31.3 | CAGI.
  3. To compute interactively, open the Compressed Air System Calculator inside WorkHive's free Engineering Design suite (link below). It runs the same method with your inputs.

FAQ

What is a compressor sizing calculator CFM kW?

The Compressed Air System Calculator is a free online tool that sizes the compressor (kW/HP) and air receiver for a plant's demand, pressure, and duty cycle. It shows the formula and a fully worked example so you can check the method, not just the number.

How is it calculated?

The result is computed from your inputs following ISO 1217 | PSME Code | ASME B31.3 | CAGI. The worked example on this page shows a real computation with real numbers.

Is the calculator free?

Yes. WorkHive is free: this worked example is open to everyone, and the interactive calculator runs inside the free Engineering Design suite after a free sign-up (your work is saved to your account). WorkHive is a free, offline-first maintenance platform built for Philippine industrial plants.

Run it on your own numbers

Open the interactive Compressed Air System Calculator in WorkHive. Free, and a free sign-up saves your calculations, BOMs and scope-of-works to your account.